In one paragraph
A rack manifold is a fabricated stainless distribution body that splits coolant supply into several branches inside a rack and collects the return. A row manifold does the same along a row, feeding the rack branches from the supply header. YiJia Cool manufactures both, together with in-rack and in-row variants, vertical and horizontal bodies, and stainless steel distribution headers, as part of the secondary-side cooling loop piping. Every body is built to the released drawing revision and approved BOM. Quick disconnects, blind-mate connectors and valves are purchased parts we integrate into the assembly, not components we manufacture.
The equipment, the packaged solution and the fabricated pipework are supplied by different parties; our liquid cooling solutions supply-scope guide sets out that split and how to write an RFQ around it.
What is a rack manifold?
A rack manifold is the last fabricated distribution point before coolant reaches the rack-level connections. Its body is a stainless header with a set of branch ports; the supply side divides flow across those ports and the return side collects it. Because the body sits inside a fixed rack envelope, its dimensions are not a product choice: they come from the rack layout, the required hose bend radius, the access space for each quick disconnect and the maintenance envelope the operator has to keep clear.
Rack manifolds are also described as in-rack manifolds. The term rack manifold refers to the position in the loop, not to a standard shape. A body can be vertical or horizontal, single-sided or with paired supply and return runs, and it may carry brackets, orientation marks, isolation positions and port labels as part of the same welded assembly. What makes it a rack manifold is where the drawing puts it and which interfaces it has to meet.
Our scope starts at the CDU outlet flange and ends at the rack interface. The piping assemblies that connect at that flange, the row bodies along the aisle and the in-rack bodies are all fabricated to the same released drawing revision, so the port geometry is reviewed as one chain rather than three separate parts.
Rack manifold vs row manifold: where each sits
Read from the CDU outlet flange toward the IT equipment: distribution header, row manifold, rack manifold, rack connection, then the return path back to the flange. The table below is the fastest way to mark up a P&ID before an RFQ goes out.
| Body | Position in the loop | What the drawing fixes |
|---|---|---|
| Stainless steel distribution header | Between the CDU outlet and the first row branch | Line size, flow rate, take-off positions, support points |
| Row manifold / in-row manifold | Along a row, feeding rack branches from the supply header | Branch count and pitch, header length, isolation positions |
| Rack manifold / in-rack manifold | Inside a rack, distributing to individual rack connections | Port count, port orientation, connection type, envelope |
| Custom welded assembly | Any position where ports, brackets and interfaces combine | Full fabrication drawing, weld map, record requirements |
Which formats do we build?
These are format names, not product numbers. The same format can look completely different on two projects because the rack envelope and the interface standard change.
| Format | Typical drawing condition | Reviewed together with |
|---|---|---|
| In-rack / rack manifold | Fixed rack envelope, limited hose bend radius, quick-disconnect access required | Rack connections, bracket positions, orientation marks |
| In-row / row manifold | Long header with repeated branches along an aisle | Supply header, isolation positions, support spacing |
| Vertical manifold | Height available, width constrained; gravity and venting noted on the drawing | Rack frame, return take-offs, handling during packing |
| Horizontal manifold | Width available, height constrained; ports face up or sideways | Cable and hose routing, maintenance envelope |
| Stainless steel distribution header | First take-offs after the CDU outlet flange | Line size, flow rate, support points |
| Custom welded assembly | Ports, brackets and interfaces combined in one body | Full fabrication drawing and weld map |
Row manifold piping and the rack bodies it feeds are reviewed as one chain. A tolerance that looks harmless on a single branch accumulates across a twelve-branch header; our note on tolerance stack-up on multi-port manifolds sets out where that shows up.
What does the specification fix before fabrication?
Most manifold problems that appear at installation were already decided, or left undecided, on the drawing. This is the checklist our engineering review works through before material is committed. It is the part of the conversation a product catalogue cannot answer.
| Decision | Why it matters | What we return at review |
|---|---|---|
| Port count and pitch | Fixes branch geometry and the space each connection needs | Fit-up conflicts, minimum spacing, bracket positions |
| Port orientation | Determines hose routing, venting and the maintenance envelope | Clashes with the rack frame or adjacent ports |
| Connection type | Sets whether the joint is pressed, welded, threaded or flanged | Tool access, hot-work restrictions, inspection method |
| Joint strategy | Follows coolant chemistry, service access and the required record | Recommended method per joint, with the trade-off stated |
| Tolerance stack-up | Small deviations accumulate across a multi-branch body | Critical dimensions and where to hold them |
| Internal surface condition | Drives cleaning, passivation and handling after fabrication | Cleaning regime and packing requirements |
| Verification and records | Belongs in the project specification, not in a catalogue | What we can record against the drawing revision |
We do not publish a universal leakage figure or a fixed acceptance limit. A number detached from the test method, the stabilisation time and the assembly volume is not meaningful. The criterion comes from the project specification; how an acceptance criterion is set explains why we ask at review rather than assume.
Why specification-built, not catalogue
Liquid cooling pipework is manufactured to specification because the loop is defined by a building, not by a product family. Rack pitch, CDU interface, coolant chemistry, the maintenance envelope and the local project specification all differ between sites. A fixed SKU would force the drawing to conform to the part; our process does the opposite.
- Receive drawing & BOM. Layout, port schedule, interfaces, material, pressure requirements and quantities arrive as one controlled package.
- Engineering review. We mark the CDU outlet flange boundary, check port geometry across the row and rack bodies, and return manufacturability questions before material is committed.
- Agree build details. Grade, wall thickness, joint method, port orientation, cleaning regime and required records are fixed against the revision.
- Fabricate & inspect. Bodies, ports, welds and fittings are built in our Foshan workshop to the released drawing.
- Clean, label & pack. Cleaning, capped ports, identification marks and protected export packing prepare the assembly for handoff.
Seamless AISI 304 / 316L stainless is the material basis; grade selection follows coolant chemistry and the required internal surface condition, not price. 304 vs 316L for coolant-wetted parts sets out how we frame that choice, and materials and fabrication describes the processes behind it. Build-to-print fabrication explains the engagement boundary in full.
Which markets do we supply?
YiJia Cool fabricates rack and row manifolds in Foshan, China and ships to the destination agreed in the order. We work with specifiers, mechanical contractors and procurement teams on data center projects in the United States and Malaysia. Enquiries, drawings, BOMs and inspection records are handled in English.
We do not maintain offices, warehouses or local certification in these markets, and we do not assume a national standard or unit system on a drawing. Country-specific requirements, acceptance criteria and documentation are taken from the project specification supplied by the customer's design team. That keeps the fabricated body tied to one controlled package regardless of where the project is built.
For the wider loop these bodies belong to, see secondary-side cooling loop piping; for the terminology behind the flange boundary, see primary loop vs secondary loop.
Interfaces we integrate but do not manufacture
UQD, blind-mate, valved connectors and customer-selected fittings are purchased components. We integrate them into a prefabricated assembly to the approved drawing so the loop can be assembled on site, and we specify the fit-up and verify the finished assembly. We do not manufacture those connectors, and we do not present their approvals as our own. Fittings and interfaces lists how those connections are specified.
The wider engagement is custom and non-standard: we analyse the drawing, propose a fit-for-purpose piping and integration solution, manufacture and factory-assemble the secondary-side piping, manifolds and integrated welded assemblies, and support on-site assembly. Final system acceptance remains with the parties named in the project specification.
Short answers before you send a drawing
Is a rack manifold a standard product?
No. Port count, pitch, orientation, connection type and acceptance criteria are set per project. We maintain format families, but each body is engineered to the approved drawing.
What is the difference between a rack manifold and a row manifold?
Position. A row manifold feeds rack branches along an aisle; a rack manifold distributes to individual connections inside one rack. Both are built to the same released drawing revision.
Can you build vertical and horizontal bodies?
Yes. Orientation follows the rack envelope and the maintenance clearances shown on the drawing, including port direction, venting and hose bend radius.
Can you work from a P&ID rather than a full CAD package?
Yes. A P&ID with flow rates, coolant type and interface points is enough for a review. We list the dimensions still needed before fabrication.
Which stainless grades do you use?
Seamless AISI 304 / 316L tube. The grade follows coolant chemistry and the required internal surface condition, not a default setting.
Which markets do you supply?
Data center projects in the United States and Malaysia, fabricated in Foshan and shipped to the destination agreed in the order. Drawings and records are handled in English.